ALUMINIUM ROUND WIRE FOR ELECTRICAL CONDUCTORS
Nom.Diam |
Tolerance |
Type of wire |
|||||
AM |
AMT |
AT |
|||||
Rm min |
A min |
Rm min |
A min |
Rm min |
A min |
||
1,5-2,0 |
0,02 |
65 |
18 |
90 |
2 |
160 |
1,3 |
2,03-2,5 |
0,03 |
||||||
2,53-3,00 |
60 |
20 |
90 |
2 |
1,5 |
||
3,02-4,00 |
0,04;-0,04 |
||||||
4,0-5,0 |
0,05;-0,05 |
25 |
3 |
2 |
|||
Resistivity at 20o C 0,0283
mm2 / m
Rm min - Tensile strength
À - elongation on 200 mm
![]()
ALUMINIUM STRANDED CONDUCTORS
TYPE AAC
Code
Sectional area,
mm2App. Overall diameter,
mmApp. mass,
kg/kmCalc. breaking load,
NDC Resistance at 20oC
/ km
Stand. length,
mDrum
A 16
15,89
5,10
43,5
2838
1,804
10000
VI
A 25
24,71
6,36
67,7
4249
1,160
7000
VI
A 35
34,36
7,50
94,1
5778
0,834
4500
VI
A 50
49,88
9,00
135,5
7944
0,579
3500
VI
A 70
69,29
10,65
189,7
10663
0,414
4000
VII
A 95
93,32
12,36
255,5
14185
0,307
3000
VII
A 120
116,99
14,00
321,9
18783
0,246
4500
IX
A 150
182,80
15,75
407,4
23351
0,195
3500
IX
A 185
182,80
17,50
503,0
28480
0,158
2800
IX
A 240
238,76
20,00
656,9
36292
0,121
2200
IX
A 300
297,57
22,40
820,4
46927
0,097
1800
IX
A 400
395,68
25,83
1090,9
60895
0,073
1300
IX
![]()
ALUMINIUM WIRE ROD
Diameter, mm |
Purity |
Electrical Resistance |
Tensile strength |
9,53 |
AL99 |
0,028035 |
59-110 MPa |
![]()
ALUMINIUM CONDUCTORS STEEL REINFORCED
TYPE AC
Code |
Sectional
area, |
App.Overall
diameter, |
App.mass, |
Calc.breaking
load, |
DC
Resistance |
Stand.length, |
Drum |
|
Al |
St |
|||||||
AC 16 |
15,27 |
2,54 |
5,40 |
61,8 |
5,83 |
1,882 |
10000 |
VI |
AC 25 |
22,81 |
3,80 |
6,60 |
92,2 |
8,65 |
1,260 |
7000 |
VI |
AC 35 |
36,95 |
6,16 |
8,40 |
149,4 |
13,39 |
0,788 |
4500 |
VI |
AC 50 |
48,88 |
8,04 |
9,60 |
195,1 |
17,01 |
0,595 |
3500 |
VI |
AC 70 |
68,05 |
11,34 |
11,40 |
275,2 |
23,59 |
0,422 |
4000 |
VII |
AC 95 |
95,3 |
15,90 |
13,50 |
385,9 |
32,98 |
0,301 |
3000 |
VII |
AC 120 |
115,32 |
21,99 |
15,16 |
493,4 |
46,58 |
0,251 |
4500 |
IX |
AC 150 |
147,52 |
26,61 |
16,96 |
616,1 |
57,18 |
0,196 |
3500 |
IX |
AC 185 |
181,14 |
34,36 |
18,98 |
773,6 |
70,47 |
0,160 |
2800 |
IX |
AC 240 |
238,03 |
43,10 |
21,56 |
1000,3 |
89,03 |
0,121 |
2200 |
IX |
AC 300 |
294,58 |
56,30 |
24,24 |
1261,4 |
110,78 |
0,098 |
1800 |
IX |
AC 400 |
395,35 |
72,23 |
27,96 |
1671,8 |
149,21 |
0,073 |
1300 |
IX |
TYPE ACO
Code |
Sectional area, mm2 |
App.Overall
diameter, mm |
App.mass, kg/km |
Calc.breaking
load, kN |
DC
Resistance at 20oC |
Stand.length, m |
Drum | |
| Al | St | |||||||
ACO 150 |
147,78 |
17,81 |
16,60 |
549,5 |
46,17 |
0,195 |
3500 |
IX |
ACO 185 |
181,14 |
21,99 |
18,40 |
674,8 |
56,24 |
0,159 |
2800 |
IX |
ACO 240 |
242,93 |
31,67 |
21,56 |
922,2 |
77,04 |
0,119 |
2200 |
IX |
ACO 300 |
291,13 |
37,17 |
23,52 |
1100,5 |
93,48 |
0,099 |
1800 |
IX |
ACO 400 |
391,95 |
49,48 |
27,24 |
1477,1 |
120,48 |
0,074 |
1300 |
IX |
TYPE ACY
Code |
Sectional area, mm2 |
App.Overall
diameter, |
App.mass, |
Calc.breaking
load, |
DC
Resistance |
Stand.length, |
Drum | |
Al |
St |
|||||||
ACY 120 |
114,04 |
26,61 |
15,40 |
526,8 |
85,31 |
0,254 |
4500 |
IX |
ACY 150 |
147,26 |
34,10 |
17,50 |
680,2 |
65,92 |
0,196 |
3500 |
IX |
ACY 185 |
184,73 |
43,10 |
19,60 |
853,3 |
81,21 |
0,157 |
2800 |
IX |
ACY 240 |
241,27 |
56,30 |
22,40 |
1114,5 |
103,11 |
0,120 |
2200 |
IX |
ACY 300 |
296,94 |
72,23 |
25,20 |
1400,5 |
134,06 |
0,097 |
1800 |
IX |
ACY 400 |
399,95 |
93,27 |
28,98 |
1854,1 |
172,18 |
0,074 |
1300 |
IX |
![]()
HOT GALVANIZED WIRE & BAND FOR LIGHTNING-CONDUCTOR INSTALATIONS
Nominal size, |
Limit tolerance, |
Tensile strength, |
Weight of the zinc-coating, |
8,0 |
+0,23/-0,23 |
up to 400 |
over 300 |
10,0 |
+0,30/-0,30 |
||
25x4,0 |
+0,15/-0,15 |
over 400 |
|
30x3,0 |
|||
35x3,5 |
|||
40x4,0 |
+0,16/-0,16 |